Mitsubishi Heavy Concealed Ducted Indoor Units.

A concealed unit performs through the ductwork and terminals connected to it. We select airflow, external static pressure, acoustic targets and maintenance access together with cooling and heating capacity.

Istanbul based · Serving the Marmara region

Mitsubishi Heavy Concealed Ducted Indoor Units

Ducted

Models in this category.

26 models

Only models in this category are listed.

26 models

Nominal capacities are listed. Model selection also depends on catalogue conditions and installation requirements.

Ducted
ModelSeriesCoolingHeatingDetails
FDU45KXE6FIndoor unitFDU high-static ducted4.5 kW5.0 kWDetails
FDU56KXE6FIndoor unitFDU high-static ducted5.6 kW6.3 kWDetails
FDU71KXE6FIndoor unitFDU high-static ducted7.1 kW8.0 kWDetails
FDU90KXE6FIndoor unitFDU high-static ducted9.0 kW10.0 kWDetails
FDU112KXE6FIndoor unitFDU high-static ducted11.2 kW12.5 kWDetails
FDU140KXE6FIndoor unitFDU high-static ducted14.0 kW16.0 kWDetails
FDU160KXE6FIndoor unitFDU high-static ducted16.0 kW18.0 kWDetails
FDU224KXZE1Indoor unitFDU large-capacity ducted22.4 kW25.0 kWDetails
FDU280KXZE1Indoor unitFDU large-capacity ducted28.0 kW31.5 kWDetails
FDUM22KXE6FIndoor unitFDUM medium-static ducted2.2 kW2.5 kWDetails
FDUM28KXE6FIndoor unitFDUM medium-static ducted2.8 kW3.2 kWDetails
FDUM36KXE6FIndoor unitFDUM medium-static ducted3.6 kW4.0 kWDetails
FDUM45KXE6FIndoor unitFDUM medium-static ducted4.5 kW5.0 kWDetails
FDUM56KXE6FIndoor unitFDUM medium-static ducted5.6 kW6.3 kWDetails
FDUM71KXE6FIndoor unitFDUM medium-static ducted7.1 kW8.0 kWDetails
FDUM90KXE6FIndoor unitFDUM medium-static ducted9.0 kW10.0 kWDetails
FDUM112KXE6FIndoor unitFDUM medium-static ducted11.2 kW12.5 kWDetails
FDUM140KXE6FIndoor unitFDUM medium-static ducted14.0 kW16.0 kWDetails
FDUM160KXE6FIndoor unitFDUM medium-static ducted16.0 kW18.0 kWDetails
FDUT15KXE6F-EIndoor unitFDUT slim ducted1.5 kW1.7 kWDetails
FDUT22KXE6F-EIndoor unitFDUT slim ducted2.2 kW2.5 kWDetails
FDUT28KXE6F-EIndoor unitFDUT slim ducted2.8 kW3.2 kWDetails
FDUT36KXE6F-EIndoor unitFDUT slim ducted3.6 kW4.0 kWDetails
FDUT45KXE6F-EIndoor unitFDUT slim ducted4.5 kW5.0 kWDetails
FDUT56KXE6F-EIndoor unitFDUT slim ducted5.6 kW6.0 kWDetails
FDUT71KXE6F-EIndoor unitFDUT slim ducted7.1 kW8.0 kWDetails

A concealed unit performs through the ductwork and terminals connected to it. We select airflow, external static pressure, acoustic targets and maintenance access together with cooling and heating capacity.

Mitsubishi Heavy Concealed Ducted Indoor Units

Technical reference

  • High-static family: FDU — Up to 200 Pa for the relevant KXE6F group, subject to model, fan and setting conditions
  • Medium-static family: FDUM — 10–100 Pa setting range in the KXE6F group; verify the duty point at required airflow
  • Example capacity: 2.8 / 3.2 kW — FDUM28KXE6F cooling / heating at ISO-T1 conditions
  • Example casing: 280 × 750 × 635 mm — FDUM28KXE6F; service and drainage space are additional

Static pressure belongs to a complete air path

Duct friction, bends, return grilles, filters and supply terminals create the resistance the fan must overcome. We calculate these losses at the required airflow. A higher pressure rating is not automatically a better choice: unnecessary fan pressure can increase noise and consumption. FDU, FDUM and slim FDUT serve different duty points.

Auto E.S.P. supports adjustment, not poor duct design

Automatic external-static-pressure control on compatible FDU and FDUM models helps the unit respond to the connected duct conditions. It cannot fix undersized ducts or unsuitable terminals. At commissioning, we measure total airflow and its distribution between rooms, then compare the settings with the design.

Give return air the same attention as supply air

A decorative slot diffuser is only the visible part of the system. Return-air free area, filter access and ceiling-void airtightness also matter. We check insulation continuity to reduce condensation risk and agree access to the fan and drain tray before the ceiling is closed.

A slim casing does not imply a long duct allowance

FDUT is evaluated for slim, low-static-pressure duct applications. Its shallow casing can help where ceiling depth is limited, but the duct resistance must remain within the model’s limits. If the airflow duty cannot be met, we revise the route, terminal layout or unit family.

Our selection checklist

  • Calculate total pressure loss at design airflow
  • Check return-air area and filter access
  • Coordinate insulation and condensate drainage
  • Measure airflow, balance branches and verify fan settings

Frequently asked questions

Will a 100 Pa unit always deliver the required air through a 100 Pa duct?

The required airflow, fan speed, adjustment range and manufacturer’s operating conditions must be checked together. Selection uses the duct system’s duty point.

Can the unit be sealed completely above the ceiling?

Filters, fans, electrical connections and drainage require maintenance access. The access arrangement belongs in the installation design.

Explore the complete system

Mitsubishi Heavy Industries VRF systemsRead the SCA Mitsubishi Heavy catalogue

Plan your system with SCA

Share your floor plan, operating hours and preferred installation locations. Our Istanbul-based team supports projects across the Marmara region, from site survey and equipment selection to installation, testing and commissioning.

We coordinate the refrigerant circuit, electrical supply, drainage, ventilation and controls as one project. Your proposal identifies the selected models, accessories and installation scope.